Shopping security
NOTICE: Product images may vary from the actual item due to differences in size or configuration options.
The Wilkins 34-ZW1070XLC is an Aqua-Gard® thermostatic mixing valve engineered for point-of-use scald protection in residential and commercial plumbing fixtures.
Key Specifications:
Other Related Variants:
Materials:
The Zurn 34-ZW1070XLC is designed for installation at single outlet points of use including fixtures, sinks, lavatories, bathtubs, and sensor faucets. The device may be used to supply individual outlets when there is sufficient supply pressure, and it is suggested to use ball valves on the hot and cold inlet supplies for optimal performance.
ASSE Listed 1070; cUPC Listed; CSA Certified B125.70; NSF/ANSI/CAN 61-9 Q≤1 (0.25% max. weighted average lead content)
Features & Benefits:
Q: What is the maximum pressure differential allowed between hot and cold water inlets?
A: The Wilkins 34-ZW1070XLC requires a maximum pressure differential of 15 psi between hot and cold inlets for proper operation.
Q: Does the outlet temperature need to be adjusted after installation?
A: Yes, the temperature must be field set during installation to achieve the desired outlet temperature within the 95-115°F range.
Q: What are the minimum and maximum flow rates for this valve?
A: The Zurn 34-ZW1070XLC has a minimum flow rate of 0.25 GPM and can achieve up to 10 GPM flow rate at 45 psi pressure loss.
NOTICE: Do not use with water that is unsafe or of unknown quality without adequate disinfection either before or after the system.